1 load lenze setting, Load lenze setting, 5drive interface – Lenze E94AxPExxxx User Manual

Page 94

Advertising
background image

5

Drive interface

5.2

Device commands

94

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.1

Load Lenze setting

The

C00002

= "0: Load Lenze setting" device command is used to reset the parameters of the active

application to the Lenze setting, which is stored in the controller firmware:

[5-12] "Load Lenze setting" function

• Only possible when the application has stopped and the controller is inhibited.
• All parameter changes made since the last saving of the parameter set will get lost!
• This device command only affects the settings of the operating system, application and module

parameters, the active application remains unchanged.

Possible status displays for this device command

Related device commands

Load start parameters

( 95)

Save start parameters

( 99)

Application 3

PS

Application 2

PS

Memory module MM

PS

9400

PS

RAM

Firmware

Application 1

Application

PS

Status (

C00003

)

Meaning

34050 Device command in process

0 Device command executed successfully

1 General error

39424 CAN fault

... ...

39679 CAN fault