C00578 | field weak. contr. reset time, C00579 | resp. to speed monitoring, C00580 | resp. to encoder open circuit – Lenze E94AxPExxxx User Manual

Page 820: Time, C00578, C00580, C00579, Rised in, Is triggered, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00578

820

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00578

C00579

C00580

Parameter | Name:

C00578 | Field weak. contr. reset time

Data type: UNSIGNED_32

Index: 23997

d

= 5DBD

h

At "240000.0 ms" the I component of the field weakening controller is deactivated.
Setting range

(min. value | unit | max. value)

Lenze setting

1.0

ms

240000.0 2000.0 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00579 | Resp. to speed monitoring

Data type: UNSIGNED_32

Index: 23996

d

= 5DBC

h

Response to activation of speed monitoring
Selection list

(Lenze setting printed in bold)

1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00580 | Resp. to encoder open circuit

Data type: UNSIGNED_32

Index: 23995

d

= 5DBB

h

Response to open circuit in encoder
Danger!

If the encoder is used as motor encoder:

In the event of an error, a safe operation of the motor cannot be ensured anymore!

For safety reasons, the "Fault" response should always be set for this case!
Selection list

(Lenze setting printed in bold)

1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble

13 Quick Stop open loop by trouble

0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1