Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

255

6

Motor interface

6.8

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• When field weakening is switched on, the actually used maximum effective motor magnetising

current is shown in

C00092

, if field weakening is switched off, "0 A" are displayed, as before.

Note!

If a Lenze motor is used:
The controller is parameterised automatically so that the field weakening works

optimally and there is no danger to the devices.

Stop!

If an OEM motor is used:
If pulse inhibit is set in the controller, the DC bus is loaded with the voltage that

corresponds to the current speed of the machine.
Since with switched-on field weakening higher speeds can be achieved at a

correspondingly higher rotor voltage of the motor, the DC bus can be loaded to a voltage

higher than the set DC-bus voltage in case of pulse inhibit and a currently high motor

speed and even exceed the maximally permissible voltage of 800 V!
In order to protect the device, either use a brake chopper, or parameterise the speed

monitoring via

C00596

and

C00607

, so that only a maximum motor speed is possible

that could also be reached with Vdc-bus = 800 V without field weakening.

Maximum motor speed

( 172)