Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

183

6

Motor interface

6.3

Adjusting motor and controller to each other

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.4

Optimising the switching performance of the inverter

An inverter generates a pulse-width-modulated, three-phase voltage system. Due to the design of

the inverter, current-dependent and switching frequency-dependent losses inside of the inverter

falsify the voltage that is output. As the voltage that is output is not measured, the losses have to

be compensated by a suitable feedforward control. This compensation is based on an inverter error

characteristic.
Among other things, the inverter error characteristic depends on the length of the motor cable and

at least has to be individually determined once for the connected motor by means of the device

command "Calculate inv. characteristic". For an automatic determination of the motor parameters,

this ensures that the current has a sinusoidal form.

Note!

Only required for servo control if the motor parameters are to be defined by a motor

from a third-party manufacturer!
Always required for sensorless vector control and open loop V/f control!

• An optimum drive performance can only be achieved with the sensorless operating

modes if the voltage errors in the inverter are compensated as exactly as possible.

Danger!

This procedure may only be carried out during commissioning, not during operation!

• During the procedure the motor is energised so that:

• it cannot be excluded that the connected mechanical components may move!
• the windings heat up.

If you repeat the procedure, ensure that the motor is not thermally overloaded

(particularly if no temperature feedback is used).

Note!

For devices of the types 6 + 7 the Ixt monitoring may be activated during the inverter

error characteristic is determined.
Remedy: Only start identification at a device utilisation (

C00066

) of 0 % and/or reduce

rated motor current (

C00088

) and reset it to the original value after the identification.