Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

321

9

I/O terminals

9.4

Digital inputs

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.4

Digital inputs

The controller is provided with eight freely configurable digital inputs.

• All digital inputs can be used for touch probe.

Touch probe detection

( 327)

• The control input RFR of terminal strip X5 for controller enable is fixedly connected to the device

control.

9.4.1

Terminal assignment/electrical data

9.4.2

Parameter setting

Short overview of parameters for the digital inputs:

Terminal

Application

Electrical data

X5/DI1

X5/DI8

Digital input 1 ... 8

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

Input current: 8 mA per input

(at 24 V)

Electric strength of

external voltage

Max. ±30 V

Conversion rate: 1 kHz

X5/RFR

Controller enable

See digital inputs

X5/GI

Reference potential (digital ground)

X5

GI

RFR

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

Parameter

Info

C00114

Digital input x - terminal pol.

C00443

Status: Digital inputs

C02803

Status word: Digital inputs

C02830

Digital inputs: Delay time

Highlighted in grey = display parameter