background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

201

6

Motor interface

6.4

Servo control (SC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.4.1.4

Optimising phase controller

How to optimise the phase controller setting by means of the ramp response:

1. Run a typical speed profile and record the ramp response of the phase controller with the

Oscilloscope

.

( 611)

• Motor control variables to be recorded:

Speed.dnSpeedSetpoint (speed setpoint)

Speed.dnActualMotorSpeed (actual speed value)

Speed.dnOutputPosCtrl (phase controller output)

Position.dnEncounteringError (following error)

2. Adjust the gain Vp of the phase controller under

C00254

and repeat oscilloscope recording

until the intended following error behaviour is reached and the motor runs sufficiently

smoothly during the constant travel phase.

3. Save parameter set (

C00002

= "11: Save start parameters").