Mxi2: wrong module [0x00680011, Incorrect memory module [0x00680012, Incorrect safety module [0x00680013 – Lenze E94AxPExxxx User Manual

Page 660: Power section was changed [0x00680014, Mxi1: module has been changed [0x00680015, 0x00680012, 0x00680013, 0x00680015, 0x00680011, 0x00680014

Advertising
background image

14

Diagnostics & fault analysis

14.7

Error messages of the operating system

660

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

MXI2: Wrong module [0x00680011]

Incorrect memory module [0x00680012]

Incorrect safety module [0x00680013]

Power section was changed [0x00680014]

MXI1: Module has been changed [0x00680015]

Module ID (decimal)

Error ID (decimal)

104: Module identification

17

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in module slot MXI2 is not

supported by the operating system.

• Use a different module.

• Please contact Lenze.

Module ID (decimal)

Error ID (decimal)

104: Module identification

18

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The memory module is not supported by the operating

system.

• Use a different module.

• Please contact Lenze.

Module ID (decimal)

Error ID (decimal)

104: Module identification

19

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safety module is not supported by the operating

system.

• Use a different module.

• Please contact Lenze.

Module ID (decimal)

Error ID (decimal)

104: Module identification

20

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The power section has been changed since the last mains

switching.

(Only information or warning locked if the hardware

type has also changed.)

Module ID (decimal)

Error ID (decimal)

104: Module identification

21

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in module slot MXI1 has been

changed since the last mains switching.

(Only information or warning locked if the hardware

type has also changed.)