6.9.3.3

Temperature monitoring of a second motor

Two motor temperature sensors can be evaluated simultaneously via the two encoder inputs X7

and X8 when two motors are used (e.g. double motor for a storage and retrieval unit). For this

purpose, the selection "X7 and X8 in parallel" must be set as feedback system for the motor

temperature in

C01193

.

• In this case, always the higher temperature of the two detected temperatures is displayed as the

current motor temperature on the Diagnostics tab and in

C00063

.

• In addition, the following display parameters exist:

C01200/1

: Motor temperature via X7

C01200/2

: Motor temperature via X8

• If one of the two detected temperatures exceeds the limit value set in

C00121

, the response set

in

C00584

is activated as advance warning.

• In the Lenze setting the "Warning" response occurs if one of the two winding temperature

exceeds 120 °C.

• As soon as one of the two detected temperatures exceeds the fixed limit value of 150 °C, the

response set in

C00583

is activated (default setting: "Fault").

• If an open circuit is detected in one of the two motor temperature sensors, the response set in

C00594

(default setting: "Fault") is activated.

• It is not possible to set different responses for the two temperature monitoring modes.
• For the motor model in the controller, the mean value of both detected temperatures is used.

Related topics:

Brake controlControl of two motor holding brakes