12.12.2.3 Standstill monitoring

After the brake closing time and the waiting time for the status monitoring have elapsed, the

standstill monitoring becomes active, i. e. the holding position is noted and compared to the

permissible angle of rotation set in

C02595

(Lenze setting: 5°) when the brake is applied.

[12-32] Automatic monitoring of the holding position

 Normal behaviour

 Error behaviour

C02591

: Waiting time - status monit.

C02595

: Permissible angle of rotation

CINH = controller inhibit

• If the stop position of the motor axis has

changed by more than the permissible

angle of rotation set in

C02595

, although

the brake is engaged:

• The error message "Motor brake:

Angular drift with closed brake too

high" is entered into the logbook.

• "Quick stop by trouble" is activated as

error response to avoid a further

rotation/acceleration of the drive.

• The error output BRK_bError is set to

TRUE for one task cycle.

• The status "position drift when brake is

applied" is displayed at the BRK_dnState

status output via bit 21 for one task

cycle.

t

t

j

BRK_bError



0

1

t

Œ

t

Stopping/Standstill

CINH



Controller enabled

Note!

The standstill monitoring can be switched off by the setting

C02595

= "0°".

The following applies to the encoderless motor control types :
If the V/f control or the sensorless vector control is selected, the standstill monitoring is

generally switched off, irrespective of the setting in

C02595

.