1 setting the error response, 14 diagnostics & fault analysis – Lenze E94AxPExxxx User Manual

Page 640

Advertising
background image

14

Diagnostics & fault analysis

14.5

Monitoring

640

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.5.1

Setting the error response

If a monitoring function responds, the response set for this monitoring function (quick stop by

trouble, warning, fault, etc.) is triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in the chapter "

Short overview (A-Z)

" contains the error messages for which the

response can be set.

( 647)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g. temperature)

has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

C00120

Motor overload protection (I²xt)

C00121

Motor temp. warning threshold

C00122

Heatsink temp. warn. threshold

C00123

Device utilisation warning threshold

C00126

CPU temp. warning threshold

C00127

Mot. overload warning threshold

C00128

Thermal time constant of motor

C00174

Undervoltage (LU) threshold

C00570

Warning thres. brake transistor

C00572

Warning thres. brake resistor

C00576

Speed monitoring tolerance

C00596

Threshold max. speed reached

C00599

Motor phase failure threshold

C00620

Max. motor current threshold