6motor interface – Lenze E94AxPExxxx User Manual

Page 232

Advertising
background image

6

Motor interface

6.6

V/f control (VFCplus)

232

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

[6-17] Voltage boost at linear/square-law V/f characteristic

Short overview: Parameters for voltage boost

Tip!
For magnetising the motor, consider a sufficient time from the controller enable to the

start of the speed ramp function generator.

• The bigger the motor the longer the time required for magnetisation. A motor with a

power of 90 kW requires up to 2 seconds.

C00090: Rated motor voltage

C00951: V/f base frequency

U

0

0

C00951

C00090

f

soll

U

Boost

0

0

C00951

f

soll

U

C00090

Œ



Œ



U

Boost

Parameter

Info

Lenze setting

Value Unit

C00960

VFC: V/f voltage boost

0 V

Advertising