8

Braking operation

8.1

Parameter setting

310

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.1

Parameter setting

Short overview: Parameters for braking operation

8.1.1

Setting the voltage threshold for braking operation

The voltage threshold for braking operation is set via

C00173

(mains voltage) and

C00181

(reduced

brake chopper threshold). If the brake chopper threshold in the DC bus is exceeded, the brake

transistor is switched on.

Parameter

Info

Lenze setting

Value Unit

C00129

Brake resistance value

180.0 Ohm

C00130

Rated brake resistor power

5600 W

C00131

Thermal capacity - brake resistor

485 kWs

C00133

Ref.: Brake chopper utilisation

Minimum resistance (C00134)

C00134

Min. brake resistance

- Ohm

C00137

Brake transistor utilisation

- %

C00138

Brake resistor utilisation

- %

C00173

Mains voltage

400/415 V

C00181

Reduc. brake chopper threshold

0 V

C00569

Resp. brake trans. ixt > C00570

Warning

C00570

Warning thres. brake transistor

90 %

C00571

Resp. brake res. i2t > C00572

Warning

C00572

Warning thres. brake resistor

90 %

C00573

Resp. to brake transistor overload

No response

C00574

Resp. to brake resist. overtemp.

No response

C00600

Resp. to DC bus overvoltage

Trouble

Highlighted in grey = display parameter

Mains voltage selected in C00173

Effective brake chopper threshold

230 V

390 V - value in

C00181

(0 ... 100 V)

400/415 V

725 V - value in

C00181

(0 ... 100 V)

460/480 V

765 V - value in

C00181

(0 ... 100 V)

500 V

790 V - value in

C00181

(0 ... 100 V)