4.4 Start-Up Flowcharts

106

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Flowchart B: Auto-Tuning for Induction Motors

The flowchart below covers Auto-Tuning for induction motors operating with V/f Control, Open Loop Vector Control, or
Closed Loop Vector Control.

Figure 4.13 Auto-Tuning for Induction Motors

<1> If an LED operator is used, the display shows “

”.

<2> If an LED operator is used, the display shows “

”.

START

Set terminals H1 and H2 if the Safe Disable function is used.

Enter the data in to T1-

parameters as indicated on the

display.

Is the Control Mode

V/f Control ?

Apply the brake if it was released during Auto-tuning.

FINISH

Can the motor

rotate freely?

Select Stationary Auto-Tuning

for Terminal Resistance only,

T1-01 = 2.

Select Stationary

Auto-Tuning 1 or 2

T1-01 = 1 or 4.

No

A1-02=2 or 3

Yes

A1-02=0

No

Yes

(Ropes removed)

Select Rotational

Auto-Tuning

T1-01 = 0.

Press the Up key until “Tuning Ready” is displayed.

Enter the data in to T1-

parameters as

indicated on the display.

Press the Up key until “Tuning Ready” is

displayed.

<1>

Release the Brake.

Close the motor contactor(s).

Press the Run key on the digital operator

and wait until Auto-Tuning is finished.

Set the Baseblock input (H1-

= 8/9) if used.

Tuning

Successful?

Refer to

Remove the source of Fault/Alarm

and repeat Auto Tuning.

Open terminals H1-HC and H2-HC if used during the normal sequence.

Open the motor contactor(s).

Open the Baseblock input (H1-

= 8/9) if used.

No

(Alarm or Fault code

displayed

Yes

(“Entry Accepted”

displayed)

<2>

<1>

Auto-Tuning Fault Detection

on page 297

.