B1-02: up/down command selection, B1-03: stopping method selection – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 157

Advertising
background image

5.2 b: Application

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

157

P

a

ra

me

te

r De

ta

ils

5

Setting 3: Option card

When b1-01 = 3, the drive looks to a serial network option card for the speed reference. Setting the speed reference from
a communication option card requires parameter d1-18 to be set to 0.

Note: 1. Be sure to program the digital inputs for speed selection and set parameter b1-01 to 0 when switching the preset speeds set in the d1-

†† parameters via a communication option card. Select the desired speed by switching these digital inputs using the drive operation
command (refer to the option card manual for details).

2. If the speed reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming

Error will be displayed on the digital operator and the drive will not run.

b1-02: Up/Down Command Selection

Determines he Up/Down command source in the REMOTE mode. Wire the motor so the elevator goes up when an Up
command is issued.

Setting 0: Operator

Allows the user to enter Up/Down commands from the digital operator. Use this setting when performing a test run only.

Setting 1: Control Circuit Terminal

Up/Down commands are issued from the control circuit terminals. This is the standard setting used in most elevator
applications.

Setting 2: MEMOBUS/Modbus Communications

This setting requires entering the Up/Down commands via serial communications by connecting the RS-485/422 serial
communication cable to control terminals R+, R-, S+, and S- on the removable terminal block.

Refer to MEMOBUS/

Modbus Configuration on page 418

for instructions.

Setting 3: Option Card

This setting requires entering the Up/Down commands via the communication option card by plugging a communication
option card into the CN5-A port on the control board. Refer to the option card manual for instructions on integrating the
drive into the communication system.

Note: If b1-02 is set to 3, but an option card is not installed in CN5-A, an oPE05 operator programming error will be displayed on the

digital operator and the drive will not run.

b1-03: Stopping Method Selection

Selects how the drive stops the motor when the Up/Down command is removed or when a Stop command is entered.

Setting 0: Ramp to stop

Ramps the motor to stop at the deceleration ramp set in C1-02. The actual time required for deceleration may vary by load
conditions (mechanical loss, inertia).

Setting 1: Coast to stop

The drive will shut off output to the motor and allow it to coast freely to stop when the Up/Down command is removed.

Setting 4: Elevator emergency stop

After the Up/Down command is cleared and when the value of U1-05 (Speed Feedback) is equal to or greater than the
value of S1-26 (Emergency Stop Start Level), the drive coasts to a stop.

After the Up/Down command is cleared and when the value of U1-05 (Speed Feedback) is lower than the value of S1-26
(Emergency Stop Start Level), the drive ramps to a stop.

No.

Parameter Name

Setting Range

Default

b1-02

Up/Down Command Selection

0 to 3

1

No.

Parameter Name

Setting Range

Default

b1-03

Stopping Method Selection

0, 1, 4

0