B2: magnetic flux compensation, B4: delay timers, B2: magnetic flux compensation b4: delay timers – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 159: B2-08: magnetic flux compensation value, Common_tmo, 2 b: application

Advertising
background image

5.2 b: Application

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

159

P

a

ra

me

te

r De

ta

ils

5

b2: Magnetic Flux Compensation

b2-08: Magnetic Flux Compensation Value

Sets the magnetic flux compensation at start as a percentage of the no-load current value (E2-03). This function allows for
the development of more flux to facilitate starting machines that require high starting torque or motors with a large rotor
time constant.

When an Up/Down command is issued, the DC current level injected into the motor changes linearly from the level set to
b2-08 to the level set to E2-03 within the time set to b2-03.

Figure 5.1

Figure 5.1 Magnetic Flux Compensation

The level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor rated current,
whichever value is smaller.

Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.

2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to S1-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.

b4: Delay Timers

The timer function is independent of drive operation and can delay the switching of a digital output triggered by a digital
input signal and help eliminate chattering switch noise from sensors. An on-delay and off-delay can be set separately.

To enable the timer function, set a multi-function input to Timer input (H1-††=18) and set a multi-function output to
Timer output (H2-††=12). Only one timer can be used.

b4-01, b4-02: Timer Function On-Delay, Off-Delay Time

b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.

No.

Parameter Name

Setting Range

Default

b2-08

Magnetic Flux Compensation Value

0 to 1000%

0%

No.

Parameter Name

Setting Range

Default

b4-01

Timer Function On-Delay Time

0.0 to 3000.0 s

0.0 s

b4-02

Timer Function Off-Delay Time

0.0 to 3000.0 s

0.0 s

E2-03

Time

S1-04

Magnetizing Current

Reference

b2-08

Output Speed

common_TMo