6.3 Fault Detection

286

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Digital Operator Display

Fault Name

PF5

Rescue Operation Power Supply Deterioration Error

Cause

Possible Solution

During Rescue Operation, either the DC bus voltage
dropped below S4-12

× (S4-13 - 10%), or 100 ms after

triggering Rescue Operation, the DC bus voltage did not
reach S4-12

× S4-13 before the motor started.

• Check the DC bus voltage setting for Rescue Operation (S4-12).
• Lower the speed reference set for Rescue Operation (d1-25).
• Check the backup power supply. It may need to be replaced with another UPS if it has become worn and can no longer provide

enough power.

Digital Operator Display

Fault Name

PGo

Encoder Disconnected (for Control Mode with Encoder)
No encoder pulses are received for longer than the time set to F1-14.

Cause

Possible Solution

Encoder cable is disconnected.

Reconnect the cable.

Encoder cable wiring is wrong.

Correct the wiring.

Encoder has no power.

Check the power line to the encoder.

Motor brake is not released.

Ensure the motor brake releases properly.

During Rescue Operation, either the DC bus voltage
dropped below S4-12

× (S4-13 - 10%), or 100 ms after

triggering Rescue Operation, the DC bus voltage did not
reach S4-12

× S4-13 before the motor started.

• Check the DC bus voltage setting for Rescue Operation (S4-12).
• Lower the speed reference set for Rescue Operation (d1-25).
• Check the backup power supply. It may need to be replaced with another UPS if it has become worn and can no longer provide

enough power.

Digital Operator Display

Fault Name

PGoH

Encoder Disconnected (detected when using an encoder)
Encoder cable is not connected properly.

Cause

Possible Solution

Encoder cable is disconnected.

Reconnect the cable.

Digital Operator Display

Fault Name

rF

Braking Resistor Fault
The resistance of the braking resistor being used is too low.

Cause

Possible Solution

The proper braking resistor option has not been
installed.

Select the braking resistor option so that fits to the drives braking transistor specification.

A regenerative converter, regenerative unit or braking
unit is being used and the +1 or +3 terminal is connected
to - terminal.

Disable the braking transistor protection selection (set L8-55 to 1).

Digital Operator Display

Fault Name

rr

Dynamic Braking Transistor Fault
The built-in dynamic braking transistor failed.

Cause

Possible Solution

The braking transistor is damaged.

• Cycle power to the drive and check if the fault reoccurs.

Refer to Diagnosing and Resetting Faults on page 304

.

• Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or a

Yaskawa representative.

The control circuit is damaged.

Digital Operator Display

Fault Name

SC

IGBT Short Circuit
Short Circuit or Ground Fault is detected

Cause

Possible Solution

IGBT fault.

• Check the wiring to the motor.
• Turn the power supply off and then on again to check operation.

If the problem continues, contact your Yaskawa representative or nearest Yaskawa sales office.

IGBT short circuit detection circuit fault.

The drive is damaged.

• Check the drive output side short circuit for broken output transistor.

B1 and U/V/W

- (negative) and U/V/W

• Contact your Yaskawa representative or nearest Yaskawa sales office.

Digital Operator Display

Fault Name

SE1

Motor Contactor Response Error
Motor contactor does not respond within the time set to S1-10 (Run Command Delay Time).

Cause

Possible Solution

There is a problem with the motor contactor or auxiliary
switch.

Check the motor contactor, auxiliary switches and the wiring of the contactor feedback signal.

Digital Operator Display

Fault Name

SE2

Starting Current Error
The output current was lower than 25% of the motor no-load current at start.

Cause

Possible Solution

The motor contactor is open.

Check the contactor for any problems.

Digital Operator Display

Fault Name

SE3

Output Current Error
The output current was lower than 25% of the motor no-load current during operation.

Cause

Possible Solution