5.3 C: Tuning

170

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

C5-01, C5-03, C5-13 / C5-02, C5-04, C5-14: Speed Control Loop Proportional Gain 1, 2, 3 /
Speed Control Loop Integral Time 1, 2, 3

These parameters adjust the responsiveness of the Speed Control Loop.

Speed Control Loop Gain Tuning (C5-01, C5-03, C5-13)

The higher this setting, the faster the speed response, although a setting that is too high can lead to oscillation.

Speed Control Loop Integral Time Tuning (C5-02, C5-04, C5-14)

Determines how fast a continuous speed deviation problem is eliminated. A setting that is too long reduces the
responsiveness of the speed control. A setting that is too short can cause oscillation.

C5-06: Speed Control Loop Primary Delay Time Constant

Sets the filter time constant for the time from the speed loop to the torque command output. Increase this setting gradually
in increments of 0.01 for loads with low rigidity or when oscillation is a problem. This parameter rarely needs to be
changed.

C5-07: Speed Control Settings Switching Speed

Sets the speed where the drive should switch between Speed Control Loop proportional gain 1, 2, and 3 (C5-01, C5-03,
and C5-13) as well as between integral time 1, 2, and 3 (C5-02, C5-04, and C5-14).

Switching Between Speed Loop Settings Accel/Decel

Switching between speed loop settings helps to achieve optimal performance and riding comfort in all sections of a trip. If
C5-07 is set higher than 0% then the speed loop settings automatically change with the output speed as shown in

Figure 5.11

and

Figure 5.12

.

Figure 5.11

Figure 5.11 Settings at Low and High Speed during Acceleration

No.

Parameter Name

Setting Range

Default

C5-01

Speed Control Loop Proportional Gain 1

0.00 to 300.00

Determined by A1-02

C5-02

Speed Control Loop Integral Time 1

0.000 to 10.000 s

Determined by A1-02

C5-03

Speed Control Loop Proportional Gain 2

0.00 to 300.00

Determined by A1-02

C5-04

Speed Control Loop Integral Time 2

0.000 to 10.000 s

0.500 s

C5-13

Speed Control Loop Proportional Gain 3

0.00 to 300.00

Determined by A1-02

C5-14

Speed Control Loop Integral Time 3

0.000 to 10.000 s

Determined by A1-02

No.

Parameter Name

Setting Range

Default

C5-06

Speed Control Loop Primary Delay Time Constant

0.000 to 0.500 s

0.004 s

No.

Parameter Name

Setting Range

Default

C5-07

Speed Control Settings Switching Speed

0.0 to 100.0%

Determined by A1-02

0

P

I

Speed

P = C5-01

I = C5-02

P = C5-03

I = C5-04

C5-07

common

_