3.9 Control I/O Configuration

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

79

El

ec

tr

ic

al

In

st

al

la

ti

o

n

3

3.9 Control I/O Configuration

Setting Sink/Source with Input Terminals SN and SP

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in

Table 3.10

(Default: Sink mode, internal power supply).

NOTICE: Damage to Equipment. Do not short terminals SP and SN. Failure to comply will damage the drive.

Table 3.10 Digital Input Sink / Source / External Power Supply Selection

Drive Internal Power Supply (Terminal SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

Sourcing Mode (PNP)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc