6.3 Fault Detection

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

283

T

ro

ubles

hoo

ting

6

Digital Operator Display

Fault Name

oFC50

Encoder Option AD Conversion Error
Error with the A/D conversion level (VCC level), or A/D conversion timed out.

Cause

Possible Solution

The PG option card is damaged.

Replace the PG option card.

Digital Operator Display

Fault Name

oFC51

Encoder Option Analog Circuit Error
Incorrect signal level (+2.5 V signal)

Cause

Possible Solution

The PG option card is damaged.

Replace the PG option card.

Digital Operator Display

Fault Name

oFC52

Encoder Communication Timeout
Signal encoder timed out waiting to receive data

Cause

Possible Solution

Encoder cable wiring is wrong.

Correct the wiring.

Encoder cable is disconnected.

Reconnect the cable.

Digital Operator Display

Fault Name

oFC53

Encoder Communication Data Error
Serial encoder CRC checksum error

Cause

Possible Solution

Encoder cable wiring is wrong.

Correct the wiring.

Encoder cable is disconnected.

Reconnect the cable.

Digital Operator Display

Fault Name

oFC54

Encoder Error
Alarm reading EnDat absolute position data from encoder

(OR flag from EnDat error for overvoltage, undervoltage, etc.)

Cause

Possible Solution

Power supply to encoder is wired incorrectly.

Correct the wiring.

The power supply circuit of the PG option card is
damaged.

Replace the PG option card.

Digital Operator Display

Fault Name

oH

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02. Default value for L8-02 is determined by
drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high.

• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy.

• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-03).

Internal cooling fan is stopped.

• Replace the cooling fan.

Refer to Cooling Fan Component Names on page 316

.

• After replacing the drive, reset the cooling fan maintenance parameter (o4-03 = 0).

Digital Operator Display

Fault Name

oH1

Heatsink Overheat
The temperature of the heatsink exceeded the drive overheat level. The overheat level is determined by drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high.

• Check the temperature surrounding the drive.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.

Load is too heavy.

• Measure the output current.
• Lower the carrier frequency (C6-03).
• Reduce the load.

Digital Operator Display

Fault Name

oH3

Motor Overheat Alarm (PTC thermistor input)

• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level.
• Detection requires multi-function analog input H3-02 or H3-10 be set to “E”.

Cause

Possible Solution

Motor thermostat wiring is fault (PTC thermistor input). Repair the PTC thermistor input wiring.
There is a fault on the machine side (e.g., the machine is
locked up).

• Check the status of the machine.
• Remove the cause of the fault.