Fault Displays, Causes, and Possible Solutions

Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-
MC. Remove the cause of the fault and manually clear the fault before attempting to run the drive again.

Table 6.8 Detailed Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

boL

Braking Transistor Overload
The braking transistor has reached its overload level.

Cause

Possible Solution

The wrong braking resistor is installed.

Make sure the rating of the braking resistor fits drive and application. Use an external braking transistor if necessary.

Digital Operator Display

Fault Name

bUS

Option Communication Error

• The connection was lost after establishing initial communication.
• Only detected when the Up/Down command speed reference is assigned to an option card.

Cause

Possible Solution

No signal was received from the PLC.

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Faulty communications wiring or an existing short
circuit.

A communications data error occurred due to noise.

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if necessary.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or on the drive input power side.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power supply input.

The option card is damaged.

Replace the option card if there are no problems with the wiring and the error continues to occur.

The option card is not properly connected to the drive.

• The connector pins on the option card do not line up properly with the connector pins on the drive.
• Reinstall the option card.

Digital Operator Display

Fault Name

CE

MEMOBUS/Modbus Communication Error
Communication data was not received for the amount of time set in parameter, H5-09 Communication Fault Detection Time.

Cause

Possible Solution

Faulty communications wiring or an existing short
circuit.

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to noise.

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or on the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power supply input.

Digital Operator Display

Fault Name

CF

Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV Control.

Cause

Possible Solution

Motor parameters are improperly set.

Check the motor parameter settings and repeat Auto-Tuning.

Torque limit is too low.

Set the torque limit to the most appropriate setting (L7-01 through L7-04).

Load inertia is too big.

• Adjust the deceleration ramp (C1-02, -04, -06, -08).
• Set the speed reference to the minimum value and interrupt the Up/Down command when the drive finishes decelerating.

Digital Operator Display

Fault Name

or

<1>

CPF00 or CPF01

Control Circuit Error

Cause

Possible Solution

There is a self diagnostic error in control circuit.

• Cycle power to the drive.
• Set the frequency to the minimum value and interrupt the Run command when the drive finishes decelerating.

Connector on the operator is damaged.

Replace the operator.

Digital Operator Display

Fault Name

CPF02

A/D Conversion Error
An A/D conversion error or control circuit error occurred.

Cause

Possible Solution

Control circuit is damaged.

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for

instructions on replacing the control board.