8.5 Installing Peripheral Devices

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

351

Per

iphe

ra

l De

vi

ce

s &

Optio

n

s

8

Connecting an AC Reactor or a DC Link Choke

Placement

When connecting to a power supply transformer with greater than 600 kVA capacity, or when switching a phase advance
capacitor, large peak current can flow through the input power supply circuit and damage converter components in the
drive.

As a preventive measure, install an AC reactor or a DC link choke to the input side of the drive. Installing an AC reactor
or a DC link choke will also help improve the power factor.

Install an AC reactor or a DC link choke if a DC drive or another type of thyristor converter is running from the same
power system, regardless of the power supply conditions shown in

Figure 8.19

.

Note: A DC link choke is built in to the drive models 2A0106 to 2A0432 and 4A0056 to 4A0260.

Figure 8.17

Figure 8.19 Installing an AC Reactor or DC Link Choke

Connecting an AC Reactor

Figure 8.18

Figure 8.20 Connecting an AC Reactor

A – Power supply

C – AC reactor

B – MCCB

D – Drive

4000

600

0

60

400

Drive Capacity (kVA)

Power Supply

Capacity (kVA)

Power supply harmonics
AC reactor or DC link choke
required

AC reactor or DC link
choke unnecessary