5.8 L: Protection Functions

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

217

P

a

ra

me

te

r De

ta

ils

5

L1-04: Motor Overheat Fault Operation Selection (PTC thermistor input)

Sets the drive operation when the PTC thermistor input signal reaches the motor overheat fault level (oH4).

Setting 0: Ramp to stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.

Setting 1: Coast to stop

The drive output is switched off and the motor coasts to stop.

Setting 2: Emergency stop (Fast stop)

The drive stops the motor using the deceleration time set in parameter C1-09.

L1-05: Motor Temperature Input Filter Time (PTC thermistor input)

Applies a filter on the PTC thermistor input signal to prevent inadvertent motor overheat faults.

L2: Undervoltage Detection

L2-05: Undervoltage Detection Level (Uv)

Determines the voltage at which a Uv1 fault is triggered. This setting rarely needs to be changed.

Note: Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage

to drive circuitry.

L3: Stall Prevention

When the load is too heavy or acceleration ramps are too short, the motor may be unable to keep up with the speed
reference, resulting in excessive slip. During acceleration, this usually causes an overcurrent fault (oC), drive overload
(oL2), or motor overload (oL1). The drive can prevent the motor from stalling and still reach the desired speed without
the user needing to change the acceleration or deceleration ramp settings. The Stall Prevention function can be set
separately for acceleration, operating at constant speeds, and deceleration.

L3-01: Stall Prevention Selection during Acceleration

Stall Prevention during acceleration (L3-01) prevents tripping with overcurrent (oC), motor overload (oL1), or drive
overload (oL2) faults common when accelerating with heavy loads.

L3-01 determines the type of Stall Prevention the drive uses during acceleration.

Setting 0: Disabled

No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.

Setting 1: Enabled

Enables Stall Prevention during acceleration.

No.

Parameter Name

Setting Range

Default

L1-04

Motor Overheat Fault Operation Selection (PTC thermistor input)

0 to 2

1

No.

Parameter Name

Setting Range

Default

L1-05

Motor Temperature Input Filter Time (PTC thermistor input)

0.00 to 10.00 s

0.20 s

No.

<1> Values shown are specific to 200 V class drives; double the values for 400 V class drives.

Parameter Name

Setting Range

Default

L2-05

<1>

Undervoltage Detection Level

150 to 210 Vdc

Determined by E1-01

No.

Parameter Name

Setting Range

Default

L3-01

Stall Prevention Selection during Acceleration

0 to 2

1