B.5 Defaults by Drive Model Selection (o2-04)

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

413

Pa

ra

met

er

L

is

t

B

B.5 Defaults by Drive Model Selection (o2-04)

The following tables show parameters and default settings that change with the drive model selection (o2-04). Parameter
numbers shown in parenthesis are valid for motor 2.

Table B.4 200 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Model CIMR-LE

2A0018

2A0022

2A0031

2A0041

2A0059

2A0075

2A0094

o2-04

Drive Model Selection

Hex.

67

68

6A

6B

6D

6E

6F

E2-11

Motor Rated Output

HP

5

7.5

10

15

20

25

30

C5-17

Motor Inertia

kgm

2

0.0158

0.0158

0.026

0.037

0.053

0.076

0.138

C6-03

Carrier Frequency

kHz

8

8

8

8

8

8

8

E2-01 (E4-

01)

Motor Rated Current

A

11.4

14

19.6

26.6

39.7

53

65.8

E2-02 (E4-

02)

Motor Rated Slip

Hz

2.7

2.73

1.5

1.3

1.7

1.6

1.67

E2-03 (E4-

03)

Motor No-Load Current

A

3.7

4.5

5.1

8

11.2

15.2

15.7

E2-05 (E4-

05)

Motor Line-to-Line Resistance

Ω

1.034

0.771

0.399

0.288

0.23

0.138

0.101

E2-06 (E4-

06)

Motor Leakage Inductance

%

19

19.6

18.2

15.5

19.5

17.2

20.1

E2-10

Motor Iron Loss for Torque Compensation

W

91

112

172

262

245

272

505

E3-08

Motor 2 Mid Output Frequency Voltage

V

16.1

16.1

16.1

16.1

16.1

16.1

16.1

E3-10

Motor 2 Minimum Output Frequency Voltage

V

8.0

8.0

8.0

8.0

8.0

8.0

8.0

E5-02

Motor Rated Power

HP

3

5

7.5

10

15

20

25

E5-03

Motor Rated Current

A

14

14.6

20

29.3

37.9

53.2

65

E5-05

Motor Stator Resistance

Ω

0.645

0.331

0.37

0.223

0.153

0.095

0.069

E5-06

Motor d-Axis Inductance

mH

7.03

4.78

5.39

3.58

3.46

2.46

1.99

E5-07

Motor q-Axis Inductance

mH

9.71

6.52

7.36

4.89

4.96

3.7

2.99

E5-09

Motor Induction Voltage Constant 1

mV/(rad/sec)

235.3

239.3

254.3

237

270

254.3

256.7

L8-02

Overheat Alarm Level

°C

110

110

120

125

120

120

125

L8-06

Input Phase Loss Detection Level

%

14.0

14.0

18.0

20.0

22.0

20.0

21.0

L8-35

Installation Method Selection

2

2

2

2

2

2

2

n5-02

Motor Acceleration Time

s

0.145

0.154

0.168

0.175

0.265

0.244

0.317

n9-60

A/D Conversion Start Delay

μsec

14.0

14.0

14.0

14.0

14.0

14.0

14.0