C.6 Communications Timing

C.6 Communications Timing

To prevent overrun in the slave drive, the master should wait a certain time between sending messages to the same drive.
In the same way, the slave drive must wait before sending response messages to prevent an overrun in the master. This
section explains the message timing.

Command Messages from Master to Drive

The master must wait for a specified time between receiving a response and re-sending the same type of command to the
same slave drive to prevent overrun and data loss. The minimum wait time depends on the command as shown in the table
below.

Table C.2 Minimum Wait Time for Sending Messages

Figure C.7

Figure C.7 Minimum Wait Time for Sending Messages

A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no
response is received within a certain amount of time, the master should try resending the message.

Response Messages from Drive to Master

If the drive receives a command from the master, it will process the data received and wait for the time set in H5-06 until
it responds. Increase H5-06 if the drive response causes overrun in the master.

Figure C.8

Figure C.8 Minimum Response Wait Time

Command Type

<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it

receives a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.

Example

Minimum Wait Time

1

• Control command (Run, Stop)
• Set inputs/outputs
• Read monitors and parameter values

5 ms

2

• Write parameters

H5-11 = 0: 50 ms

H5-11 = 1: 200ms

<1>

3

• Save changes using an Enter command

200 ms to 2 s, depending on the number of

parameters that were changed

<1>

Command message

Response message

Command message

PLC→Drive

PLC→Drive

Drive→PLC

24 bit length

Master Send
Wait Time

Time

common

TMonly

Time

Command message

Response message

Command message

PLC→Drive

PLC→Drive

Drive→PLC

24 bit length

H5-06
setting

common

TMonly