Output terminals, Yea_common, 8 control circuit wiring – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 74: Table 3.6 control circuit output terminals

Advertising
background image

3.8 Control Circuit Wiring

74

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Output Terminals

Table 3.6

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function

output.

Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler

outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.

Table 3.6 Control Circuit Output Terminals

Figure 3.17

Figure 3.18 Connecting a Suppression Diode

Analog Inputs

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

156

-V

Power supply for analog inputs

-10.5 Vdc (max allowable current 20 mA)

A1

Multi-function analog input 1 (Speed reference bias)

-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k

Ω)

156
193

A2

Multi-function analog input 2 (Not used)

-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k

Ω)

156
193

AC

Analog input common

0 V

156

E (G)

Ground for shielded lines and option cards

<1> Setting jumper S3 for an external power supply makes the wire jumper between terminals H1, H2, and HC ineffective. Remove the wire jumper

and connect an external power supply that can supply terminals H1, H2, and HC continuously.

Type

<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.

Switching life is estimated at 200,000 times (assumes 1 A, resistive load).

<2> Connect a suppression diode as shown in

Figure 3.18

when driving a reactive load such as a relay coil. Make sure the diode rating is greater

than the circuit voltage.

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Fault Relay

MA

N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

193

MB

N.C. output

MC

Fault output common

Multi-Function
Relay Output

<1>

M1

Multi-function relay output 1 (Brake release command)

Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

193

M2

M3

Multi-function relay output 2 (Output contactor close command)

M4

M5

Multi-function relay output 3 (Drive ready)

M6

Multi-Function
Photocoupler
Output

P1

Photocoupler output 1 (During Frequency output)

48 Vdc, 2 to 50 mA

<2>

C1

P2

Photocoupler output 2 (Not Used/Through Mode)

C2

Monitor Output

FM

Analog monitor output 1 (Output speed)

-10 to +10 Vdc or 0 to +10 Vdc

193

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

Safety Monitor
Output

DM+

Safety monitor output

Outputs status of Safe Disable function. Closed when both Safe Disable
channels are closed. Up to +48 Vdc 50 mA

DM-

Safety monitor output common

A – External power, 48 V max.

C – Coil

B – Suppression diode

D – 50 mA or less

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

A

B

C

D

YEA_common

Advertising