5.7 H: Terminal Functions

198

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Table 5.12 Multi-Function Digital Output Terminal Settings

Setting 0: During Run

Output closes when the drive is outputting a voltage.

Setting 1: Zero Speed

Terminal closes whenever the output speed or motor speed (CLV, CLV/PM) becomes less than the minimum output speed
set to E1-09 or S1-01.

Note: When using CLV or CLV/PM control modes, the output terminal will close when the motor speed becomes less than or equal to

the zero speed level set for S1-01. In all other control modes, the output terminal will close when the output frequency becomes
less than or equal to the minimum output frequency set for E1-09.

Figure 5.18

Figure 5.18 Zero-Speed Time Chart

H2-05

Terminals P2-C2 Function Selection (photocoupler)

0 to 161

F: Through Mode

Setting

Function

Page

Setting

Function

Page

0

During Run

198

1B

During Baseblock 2 (N.C.)

204

1

Zero Speed

198

1C

Motor 2 Selection

205

2

Speed Agree 1

199

1D

During Regeneration

205

3

User-set Speed Agree 1

200

1E

Restart Enabled

205

4

Speed Detection 1

200

1F

Motor Overload Alarm (oL1)

205

5

Speed Detection 2

200

20

Drive Overheat Pre-alarm (oH)

205

6

Drive Ready (READY)

201

2F

Maintenance Period

205

7

DC Bus Undervoltage

201

30

During Torque Limit

205

8

During Baseblock (N.O.)

201

33

Within Position Lock Bandwidth

205

9

Speed Reference Source

201

37

During Frequency Output

205

A

Up/Down Command Source

201

50

Brake Control

206

B

Torque Detection 1

202

47

Input Phase Loss

206

E

Fault

202

4E

Braking Transistor Fault (rr)

206

F

Not used (Through Mode)

202

51

Output Contactor Control

206

10

Minor Fault

202

52

Door Zone Reached

206

11

Fault Reset Command Active

202

53

Not Zero Speed

206

12

Timer Output

202

54

Light Load Direction

206

13

Speed Agree 2

202

55

Light Load Direction Detection Status

206

14

User-set Speed Agree 2

203

58

Safe Disable Status

206

15

Speed Detection 3

203

5C

Motor Current Monitor

206

16

Speed Detection 4

204

60

Internal Cooling Fan Alarm

206

18

Torque Detection 2

202

61

Motor Pole Search Status

207

1A

During Reverse

204

100 to 161

Functions 0 to 61 with Inverse Output

207

Status

Description

Open

Drive is stopped.

Closed

An Up/Down command is input or the drive is during deceleration or during DC injection.

Status

Description

Open

The operating speed is greater than the minimum output frequency (E1-09) or the zero speed level at stop (S1-01).

Closed

The operating speed is less than or equal to the minimum output frequency (E1-09) or the zero speed level at stop (S1-01).

No.

Parameter Name

Setting Range

Default

OFF

Output speed

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
S1-01 (Zero Speed Level)

common

TMonly