C.5 Drive Operations by MEMOBUS/Modbus

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

425

MEMOBUS

/Mo

dbu

s

C

o

m

m

u

ni

ca

ti

on

s

C

C.5 Drive Operations by MEMOBUS/Modbus

The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings.
This section explains the functions that can be used and related parameter settings.

◆ Observing the Drive Operation

A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except H5-††).

• Observe drive status and drive control terminal status from a PLC.
• Read and write parameters.
• Set and reset faults.
• Set multi-function inputs.

Note: Input settings from the input terminals S† and from MEMOBUS/Modbus communications are both linked by a logical OR

operation.

◆ Controlling the Drive

Select an external reference and adjust the parameters in

Table C.1

accordingly to start and stop the drive or set the

frequency reference using MEMOBUS/Modbus communications.

Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus

Refer to b1-01: Speed Reference Selection on page 156

and

Refer to b1-02: Up/Down Command Selection on page 157

for details on operation mode parameter selections.

Reference Source

Parameter

Name

Required Setting

External Reference

b1-01

Speed Reference Selection

2

b1-02

Up/Down command Selection

2