4.8 Verifying Parameter Settings and Backing Up Changes

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

147

St

ar

t-

U

p

Pr

og

ra

m

m

in

g

&

Op

er

at

io

n

4

4.8 Verifying Parameter Settings and Backing Up Changes

Use the Verify Menu to check all changes to parameter settings as a result of Auto-Tuning.

Refer to Verifying Parameter

Changes: Verify Menu on page 98

.

Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental
modification of parameter settings.

Backing Up Parameter Values: o2-03

Setting o2-03 to 1 saves all parameter settings before resetting o2-03 to 0. The drive can now recall all the saved
parameters by performing a User Initialization (A1-03 = 1110).

Parameter Access Level: A1-01

Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1-†† and U†-††
only. Other parameters are not displayed.

Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application.

Password Settings: A1-04, A1-05

The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01,
A1-02, A1-03 and A2-01 through A2-33.

Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and press

and

simultaneously.

No.

Parameter Name

Description

Setting Range Default Setting

o2-03

User Parameter
Default Value

Lets the user create a set of default settings for a User Initialization.
0: Saved/Not Set
1: Set Defaults - Saves current parameter settings as the default values for a User Initialization.
2: Clear All - Clears the currently saved user settings. After saving the user parameter set value, the items of
1110 (User Initialization) are displayed in A1-03 (User Parameter Default Value).

0 to 2

0

A1-03

Initialize Parameters

Selects a method to initialize the parameters.
0: No Initialize
1110: User Initialization (The user must first program and store desired settings using parameter o2-03)
2220: 2-Wire Initialization (parameter initialized prior to shipment)
5550: oPE4 Fault reset

0 to 2220, 5550

0

No.

Parameter

Name

Description

Setting

Range

Default

A1-01

Access Level
Selection

Selects which parameters are accessible via the digital operator.
0: Operation only. A1-01, A1-04, and A1-06 can be set and monitored, and U†-†† parameters can also be viewed.
1: User Parameters. Only recently changed parameters from application parameters A2-01 to A2-16 and A2-17 to A2-32
can be set and monitored.
2: Advanced Access Level. All parameters can be set and monitored.

0 to 2

2

A2-01

to

A2-32

User Parameters
1 to 32

Parameters selected by the user are saved as User Parameters, including recently viewed parameters and parameters

specifically selected for quick access.
If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32. Parameters A2-01
through A2-16 must be manually selected by the user.
If A2-33 is set to 0, recently viewed parameters will not be saved to the group of User Parameters. A2-†† parameters
are now available for manual programming.

A1-00 to

o4-13

A2-33

User Parameter
Automatic Selec-
tion

0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for
quick access. The most recently changed parameter is saved to A2-17. The second most recently changed parameter is
saved to A2-18.

0, 1

1