5.4 d: Reference Settings

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

175

P

a

ra

me

te

r De

ta

ils

5

d1-19: Nominal Speed

Sets the nominal speed when a multi-function input terminal is programmed for “Nominal speed” (H1-†† = 50).

d1-20, d1-21, d1-22: Intermediate Speeds 1 to 3

Sets intermediate speeds 1 through 3.

d1-23: Releveling Speed

Sets the releveling speed when a multi-function input terminal is programmed for “Releveling speed” (H1-†† = 52).

d1-24: Inspection Operation Speed

Sets the inspection speed when a multi-function input terminal is programmed for “Inspection speed” (H1-†† = 54). A
description of the inspection speed can be found in

Inspection Operation on page 124

.

d1-25: Rescue Operation Speed

Determines the speed during Rescue Operation.

Refer to Rescue Operation on page 131

for details.

d1-26: Leveling Speed

Sets the inspection speed when a multi-function input terminal is programmed for “Leveling speed” (H1-†† = 53).

No.

Parameter Name

Setting Range

Default

d1-19

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Nominal Speed

0.00 to 100.00%

<1>

100.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-20

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Intermediate Speed 1

0.00 to 100.00%

<1>

0.00%

<1>

d1-21

Intermediate Speed 2

0.00 to 100.00%

<1>

0.00%

<1>

d1-22

Intermediate Speed 3

0.00 to 100.00%

<1>

0.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-23

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Releveling Speed

0.00 to 100.00%

<1>

0.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-24

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Inspection Operation Speed

0.00 to 100.00%

<1>

50.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-25

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Rescue Operation Speed

0.00 to 100.00%

<1>

10.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-26

<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit

Selection (o1-03) on page 416

for details.

Leveling Speed

0.00 to 100.00%

<1>

8.00%

<1>