5.2 b: Application

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

161

P

a

ra

me

te

r De

ta

ils

5

b7-01: Droop Control Gain

Sets the amount of speed reduction when the torque reference is 100%. The gain is set as a percentage of the maximum
output speed. A setting of 0.0% disables the Droop control function.

Figure 5.4

Figure 5.4 Droop Control Gain

b7-02: Droop Control Delay Time

Adjusts the responsiveness of Droop control. Reduce the setting if the reaction time is too long, and increase it if hunting
occurs.

b8: Energy Saving

The Energy Saving function can significantly increase the efficiency of an IPM motor.

Note: The Energy Saving function should be used only with a Yaskawa IPM motor.

b8-01: Energy Saving Control Selection

Enables or disables the Energy Saving function.

Setting 0: Disabled
Setting 1: Enabled

b8-16: Energy Saving Control Constant (Ki)

Enter the Energy Saving value (Ki) as specified on the motor nameplate (for IPM motors only).

b8-17: Energy Saving Control Constant (Kt)

Enter the Energy Saving value (Kt) as specified on the motor nameplate (for IPM motors only).

No.

Parameter Name

Setting Range

Default

b7-01

Droop Control Gain

0.0 to 100.0%

0.0%

No.

Parameter Name

Setting Range

Default

b7-02

Droop Control Delay Time

0.03 to 2.00 s

0.05 s

No.

Parameter Name

Setting Range

Default

b8-01

Energy Saving Control Selection

0 or 1

0

No.

Parameter Name

Setting Range

Default

b8-16

Energy Saving Control Constant (Ki)

0.00 to 2.00

0.10

No.

Parameter Name

Setting Range

Default

b8-17

Energy Saving Control Constant (Kt)

0.00 to 2.00

1.00

Speed

Torque

100%

Speed reference

Droop control gain

b7-01

0

common_TMo