5.11 S: Elevator Parameters

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

261

P

a

ra

me

te

r De

ta

ils

5

Leveling Distance Control

Leveling Distance Control (S5-10 = 2) uses the leveling speed reference for the remaining distance to arrive at the
designated floor. Leveling Distance Control is activated when the conditions listed in

Table 5.16

are met.

Table 5.16 Leveling Distance Control Operation

Figure 5.50 Operation Sequence Example for Leveling Distance Control

S5-10: Stopping Method Selection

Selects the stopping method.

Setting 0: Disable
Setting 1: Direct Landing
Setting 2: Leveling Distance Control

S5-11: Deceleration Distance

Sets the deceleration distance when Stop Distance Control is enabled.

Refer to Direct Landing on page 260

for details.

Speed Priority Selection

Multi-Function Input Terminal Settings

Leveling Distance Control Start Conditions

Multi-step speed sequence

(d1-18 = 0, 3)

The Up/Down command is not active or the speed reference is 0.

High speed reference has priority

(d1-18 = 1)

Leveling speed reference is selected

(H1-†† = 53).

The Up/Down command is not active, or all input terminals set for

H1-†† = 50 to 53 are open.

Leveling speed reference is not selected

(H1-††

≠ 53).

Up/Down command is not active.

Multi-step speed sequence

(d1-18 = 2)

Rated speed reference is selected

(H1-†† = 50).

The Up/Down command is not active, or all input terminals set for

H1-†† = 50 to 53 are open.

Rated speed reference is not selected

(H1-††

≠ 50).

Up/Down command is not active.

<1> Area S is the stopping distance (S5-12) from the point at which leveling operation is complete to when the car arrives at the designated

floor.

No.

Parameter Name

Setting Range

Default

S5-10

Stopping Method Selection

0 to 2

0

No.

Parameter Name

Setting Range

Default

S5-11

<1> The setting range becomes 0.00 to 650.00 inches when the length units are set for inches (o1-12 = 1).

Deceleration Distance

0 to 32767 mm

<1>

0 mm

Operation
Speed

Time

ON

OFF

OFF

OFF

OFF

ON

ON

ON

Run Command Delay Time (S1-10)

Brake Release Delay Time

Brake Close
Delay Time

ON

Zero Speed

at Start

(S1-06)

Zero Speed

at Stop

(S1-07)

Output Contactor Open
Delay Time (S1-11)

Run Command
(Forward [Up] / Reverse [Down])

H2-

= 53 (Not Zero Speed

)

H2-

= 51

(Output Contactor Control

)

H1-

= 56

(Motor Contactor Feedback

)

H2-

= 50 (Brake Control

)

S

<1>