6 setup procedure for elevator applications, Refer to figure 4.25 for a wiring diagram, Starting rescue operation 1 – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 133: Ending rescue operation 1

Advertising
background image

4.6 Setup Procedure for Elevator Applications

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

133

St

ar

t-

U

p

Pr

og

ra

m

m

in

g

&

Op

er

at

io

n

4

Using a Single-Phase, 230 Vac UPS (Uninterruptable Power Supply)

Follow the instructions when using a single-phase 230 V UPS for Rescue Operation. A 230 V UPS can be used for both
200 V and 400 V class drives.

Wiring

Refer to

Figure 4.25

for a wiring diagram.

Figure 4.20

Figure 4.25 Using a Single-Phase 230 V UPS

Operation Sequence

Starting Rescue Operation

1.

Open contactor B.

2.

Set the input terminal programmed for Rescue Operation (H1-†† = 55).

3.

Close contactor A.

4.

Set the Up/Down command.

Ending Rescue Operation

1.

After the car has stopped open contactor A.

2.

Clear the input terminal set for Rescue Operation (H1-†† = 55).

3.

Close contactor B to return to operation with normal power supply.

Application Precautions

The drive may fault on a control power supply fault (Uv2) if the UPS can’t provide enough voltage, or if the Light Load
Direction Search is not set properly. If this problem occurs, take the following corrective actions:

Corrective Action:

• Use a separate battery for the controller power supply.

-

L1000E

Magnetic Contactor Sequence

H1-

ڧڧ = 55

(Rescue Operation)

sine wave
230 Vac
single-phase

H1-

ڧڧ = 55

(Rescue Operation)

L1

L2

L3

N

R/L1

S/L2

T/L3

CN19

S

3

to S

8

1

4

SC

+1

+2

B2

W/T3

V/T2

U/T1

Magnetic
Contactor B

Magnetic
Contactor A

UPS

Magnetic Contactor B

Magnetic Contactor A

Elevator

control

system

Control

circuit

Power supply

Advertising