D.2 UL Standards

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

455

St

an

dar

d

s

Complianc

e

D

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your Yaskawa representative for instructions.

Guarding Against Harmful Materials

When installing IP00 enclosure drives, use an enclosure that prevents foreign material from entering the drive from above
or below.

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. If external
power supply used, it shall be UL Listed Class 2 power source only or equivalent. Refer to NEC Article 725 Class 1,
Class 2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements concerning class 1 circuit
conductors and class 2 power supplies.

Table D.5 Control Circuit Terminal Power Supply

Drive Short Circuit Rating

This drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes,

480 Vac maximum (Up to 240 V in 200 V class drives, up to 480 V for 400 V class drives), when protected by fuses or
circuit breakers as specified in

Table D.4

.

2A0354

125

271

500

450

800

FWH-700A (700)

2A0432

150

324

600

500

900

<5>

FWH-800A (800)

480 V Models

4A0009

5

8.2

15

12

20

FWH-90B (90)

4A0012

7.5

10.4

20

17.5

30

FWH-90B (90)

4A0019

10

15

30

25

40

FWH-80B (80)

4A0023

15

20

40

35

60

FWH-100B (100)

4A0030

20

29

50

50

80

FWH-125B (125)

4A0039

25

39

75

60

110

FWH-200B (200)

4A0049

30

44

75

75

125

FWH-250A (250)

4A0056

40

43

75

75

125

FWH-250A (250)

4A0075

50

58

100

100

150

FWH-250A (250)

4A0094

60

71

125

110

200

FWH-250A (250)

4A0114

75

86

150

150

250

FWH-250A (250)

4A0140

100

105

175

175

300

FWH-350A (350)

4A0188

125

142

225

225

400

FWH-400A (400)

4A0225

150

170

250

250

500

FWH-500A (500)

4A0260

175

207

350

350

600

FWH-600A (600)

<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.

<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.

<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.

<4> When using semiconductor fuses, Bussmann FWH is required for UL compliance.

<5> Class L fuse is also approved for this rating.

Input / Output

Terminal Signal

Power Supply Specifications

Open Collector Outputs

P1, C1, P2, C2, DM+, DM-

Requires class 2 power supply

Digital inputs

S1-S8, SN, SC, SP, HC, H1, H2

Use the internal LVLC power supply of the drive. Use class 2 for
external power supply.

Analog inputs / outputs

+V, -V, A1, A2, AC, AM, FM

Drive Model

CIMR-LE

L1000E

Nominal Output

Power HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay Fuse

Rating Amps

<2>

Non-time Delay

Fuse Rating Amps

<3>

Bussmann

Semi-conductor Fuse Rating

(Fuse Ampere)

<4>