5.9 n: Special Adjustments

238

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Other Settings

Parameters n8-29 to n8-33 can be used to adjust the current control loop. Adjustment is not normally required.

Parameter n8-62 sets a voltage limit in order to prevent voltage saturation.

n8-29: q-Axis Current Control Gain during Normal Operation

Sets the q-Axis proportional gain for the automatic current regulator.

n8-30: q-Axis Current Control Integral Time during Normal Operation

Sets the q-Axis integral time for the automatic current regulator.

n8-32: d-Axis Current Control Gain during Normal Operation

Sets the d-Axis proportional gain for the automatic current regulator.

n8-33: d-Axis Current Control Integral Time during Normal Operation

Sets the d-Axis integral time for the automatic current regulator.

n8-62: Output Voltage Limit

Sets the output voltage limit to prevent voltage saturation of the motor. Avoid setting this value higher than the input
voltage on the motor nameplate to maintain optimum motor performance.

n9: Current Detection Adjustments

n9-60: A/D Conversion Start Delay

Sets a delay time used for A/D conversion of the current. This value rarely needs to be changed. However, it can help to
resolve speed ripple problems at constant speed when using a PM motor. Prior to adjusting this value, make sure all other
parameters (motor data, speed loop settings) are adjusted correctly.

No.

Parameter Name

Setting Range

Default

n8-29

q-Axis Current Control Gain during Normal Operation

0 to 2000 rad/s

1000 rad/s

No.

Parameter Name

Setting Range

Default

n8-30

q-Axis Current Control Integral Time during Normal Operation

0.0 to 100.0 ms

10.0 ms

No.

Parameter Name

Setting Range

Default

n8-32

d-Axis Current Control Gain during Normal Operation

0 to 2000 rad/s

1000 rad/s

No.

Parameter Name

Setting Range

Default

n8-33

d-Axis Current Control Integral Time during Normal Operation

0.0 to 100.0 ms

10.0 ms

No.

<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.

Parameter Name

Setting Range

Default

n8-62

<1>

Output Voltage Limit

0.0 to 230.0 Vac

200 Vac

No.

Parameter Name

Setting Range

Default

n9-60

A/D Conversion Start Delay

0.0 to 40.0

μs

Determined by o2-04