C.7 Message Format

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

427

MEMOBUS

/Mo

dbu

s

C

o

m

m

u

ni

ca

ti

on

s

C

C.7 Message Format

Message Content

In MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The message
format is configured for both sending and receiving as shown below, and the length of data packets depends on the
command (function) content.

Slave Address

The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a
message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves
do not provide a response to a broadcast type message.

Function Code

The three types of function codes are shown in the table below.

Data

Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test)
and the data the register contains. The data length changes depending on the command details.

A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers
must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.

Function

Code

Function Name

Data Length (bytes)

Command Message

Response Message

Minimum

Maximum

Minimum

Maximum

03H

Read MEMOBUS/Modbus registers

8

8

7

37

08H

Loopback test

8

8

8

8

10H

Write to multiple MEMOBUS/Modbus registers

11

41

8

8

SLAVE ADDRESS

FUNCTION CODE

DATA

ERROR CHECK