S1-05: dc injection / position lock time at stop, S1-06: brake release delay time, S1-07: brake close delay time – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 249: S1-10: run command delay time, S1-11: output contactor open delay time, 11 s: elevator parameters

Advertising
background image

5.11 S: Elevator Parameters

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

249

P

a

ra

me

te

r De

ta

ils

5

S1-05: DC Injection / Position Lock Time at Stop

Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM, S1-05 determines how long
Position Lock should be performed. A setting of 0.00 disables S1-05.

S1-06: Brake Release Delay Time

Determines the time that must pass after an Up/Down command is entered before the output terminal set for "Brake
control" (H2-†† = 50) is triggered.

Adjusting this delay time can help when there is not enough time to develop the appropriate amount of motor flux. Be
sure to also increase the time S1-04 when setting S1-06 to relatively long delay time.

S1-07: Brake Close Delay Time

Determines the time that must pass after zero speed is reached before the output terminal set for "Brake control"

(H2-†† = 50) is released.

S1-10: Run Command Delay Time

Sets the time the drive waits after receiving an Up/Down command before starting operation. The time set should give the
motor contactor enough time to close.

S1-11: Output Contactor Open Delay Time

Determines the time that must pass for an output terminal set for “Output contactor control” (H2-†† = 51) to be released
after the drive has stopped and drive output has been shut off.

S1-12: Motor Contactor Control During Auto-Tuning Selection

Determines the state of the output contactor control command (H2-†† = 51) during Auto-Tuning. The contactor closes
as soon as the Enter key is pressed in the Auto-Tuning start menu.

WARNING! Sudden Movement Hazard.Use parameter S1-12 to enable/disable automatic switching of the Motor Contactor Control

output signal during Auto-Tuning. When using setting S1-12 = 1, ensure that the multi-function output terminals are properly wired and

in the correct state before setting parameter S1-12. Failure to comply could result in damage to the drive, serious injury or death.

No.

Parameter Name

Setting Range

Default

S1-05

DC Injection / Position Lock Time at Stop

0.00 to 10.00 s

0.60 s

No.

Parameter Name

Setting Range

Default

S1-06

Brake Release Delay Time

0.00 to 10.00 s

0.20 s

No.

Parameter Name

Setting Range

Default

S1-07

Brake Close Delay Time

0.00 to [S1-05]

0.10 s

No.

Parameter Name

Setting Range

Default

S1-10

Run Command Delay Time

0.00 to 1.00 s

0.10 s

No.

Parameter Name

Setting Range

Default

S1-11

Output Contactor Open Delay Time

0.00 to 1.00 s

0.10 s

No.

Parameter Name

Setting Range

Default

S1-12

Motor Contactor Control during Auto-Tuning

0 to 2

0