L8-89: Current Monitoring Selection
Enables and disables the Current Monitoring function. When this parameter is set to 1 (Enabled), the current monitoring
level (L8-99) is added to the conditions required to turn off the Motor Contactor Feedback command at a stop.
Setting 0: Disabled
Setting 1: Enabled
■
L8-99: Current Monitoring Level
Sets the current monitoring level as a percentage of the drive's rated current. When the output current is equal to or below
the set level, the Motor Contactor Feedback command turns off. This parameter is also used to activate the Motor Current
Monitor (H2-
= 5C).
No.
Parameter Name
Setting Range
Default
L8-89
Current Monitoring Selection
0, 1
0
No.
Parameter Name
Setting Range
Default
L8-99
Current Monitoring Level
0.0 to 50.0 %
10.0 %