4.6 Setup Procedure for Elevator Applications

132

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Table 4.13 Power Supply Ratings for Rescue Operation

Parameter Setup

Adjust drive parameters as described below when using Rescue Operation.

• Select the type of Rescue Operation power supply for the drives main circuit in parameter S4-06.
• When using a UPS, set the UPS power value to parameter S4-07. Use parameter S4-08 to decide if the Rescue

Operation speed shall be limited automatically depending on the UPS power.

• If deterioration of the battery or UPS shall be detected, also set up parameters S4-12 and S4-13. Measure the DC bus

voltage during operation using the rescue power supply and set the measured value to parameter S4-12. Set the
deterioration detection level to parameter S4-13.

• Set parameters S4-01 to S4-04 if light load direction search shall be automatically performed when Rescue Operation is

started.

Wiring Examples

Switching the main power supply to a battery or UPS requires magnetic contactors that must be controlled by an external
controller. Wiring methods and the sequence used for the magnetic contactors depend on the application. This instruction
manual describes the following configurations:

• A single-phase, 230 V UPS is used as backup power supply for a 200 V or 400 V class drive.
• Two separate batteries for the main power and control power supplies. Main power battery voltage is below 250 Vdc for

200 V class drives or 500 Vdc for 400 V class drives.

• Two separate batteries. One is used for the main power supply, a second battery supplies the controller via an optional

24 V Backup Power Supply Unit.

• A single battery with minimum 250 Vdc for 200 V class drives or 500 Vdc for 400 V class drives is used for the main

and control power supply.

Select the configuration that matches your application. Follow the corresponding instructions for wiring and drive
settings. For configurations not covered in the list above, contact your Yaskawa representative or our sales office directly
for consultation.

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Never remove or install option cards or

attempt to replace the cooling fan while the drive is switched on. Make sure that the drive and all devices connected to the drive have

been shut off prior to performing and type of maintenance or wiring. After shutting off the power, wait for at least the amount of time

specified on the drive before touching any components or perform wiring. The internal capacitor remains charged even after the power

supply is turned off.

NOTICE: Be sure to thoroughly read the instructions for wiring and magnetic contactor sequence described in this section before

setting up the drive for Rescue Operation. Failure to follow these instructions can damage the drive.

NOTICE: Refrain from using Rescue Operation for extend periods of time. Rescue Operation uses a low DC bus voltage, which can

cause the cooling fan to shut off temporarily during Rescue Operation. Continuing to operate under these conditions can trigger an

overheat fault and damage the drive.

Motor Type

Speed Feedback

DC Bus Voltage

Control Circuit Voltage

Induction Motor

Incremental PG Encoder with PG-X3 option
card

200 V class drives: 48 to 340 Vdc
400 V class drives: 96 to 680 Vdc

When supplied from a battery or the drive DC bus:
200 V class drives: 250 to 340 Vdc
400 V class drives: 280 to 680 V (recommended: 500 to 680 Vdc)

When supplied via a 24 Vdc control power backup unit:
200 V and 400 V class drives: 24 Vdc

Permanent Magnet Motor

Incremental PG Encoder with PG-X3 option
card
“End8” to “End10” error occurs during Initial
Magnet Pole Search Auto-Tuning.

200 V class drives: 280 to 340 Vdc
400 V class drives: 560 to 680 Vdc

Incremental PG Encoder with PG-X3 option
card
No error occurs during Initial Magnet Pole
Search Auto-Tuning.

200 V class drives: 72 to 340 Vdc

400 V class drives: 144 to 680 Vdc

Absolute PG Encoder with PG-F3 or PG-E3
option card

200 V class drives: 48 to 340 Vdc
400 V class drives: 96 to 680 Vdc