C.4 MEMOBUS/Modbus Setup Parameters

424

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

Setting 0: 0.1 V units
Setting 1: 1 V units

H5-11: Communications Enter Function Selection

Selects whether an Enter command is necessary is needed to change parameter values via MEMOBUS/Modbus
communications.

Refer to Enter Command on page 442

.

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last
parameter change, not for each single parameter.

Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

No.

Parameter Name

Setting Range

Default

H5-10

Unit Selection for MEMOBUS/Modbus Register 0025H

0 or 1

0

No.

Parameter Name

Setting Range

Default

H5-11

Communications Enter Function Selection

0 or 1

0