4.6 Setup Procedure for Elevator Applications

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

123

St

ar

t-

U

p

Pr

og

ra

m

m

in

g

&

Op

er

at

io

n

4

Higher Speed Priority is Selected and the Leveling Speed Input is Not Assigned (d1-18 = 1 and H1-††

53)

The drive decelerates to the leveling speed (d1-26) when the selected speed reference signal is removed.

If no speed reference is selected at start, the drive will trigger an “FrL” fault. Set parameter S6-15 to 0 to disable Speed
Reference Missing (FrL) detection. With this setting the drive starts using leveling speed if no other speed reference is
selected.

Leveling Speed has Priority and the Leveling Speed Input is Assigned (d1-18 = 2, H1-†† = 53)

The leveling signal has priority over other speed references. The drive decelerates to the leveling speed (d1-26) when the
leveling speed selection input is activated. The drive stops when either the leveling input or the Up/Down command is
released.

Leveling Speed Priority is Selected and the Nominal Speed Input is Not Assigned (d1-18 = 2, H1-††

50)

The drive runs at nominal speed (d1-19) when no speed selection input is set. When the leveling speed signal is set, the
drive decelerates to the leveling speed. The leveling speed signal has priority over all other speed signals.

NOTICE: Equipment Hazard. This function may not work properly if a broken wire connection to the drive I/O causes improper elevator

speed selection. Properly tighten wire connections at the drive terminals before enabling this function.

Multi-Function Terminal Setup

Multi-Function Digital Input (Terminals S3 to S8)

The H1 parameters assign functions to digital input terminals S3 to S8 digital input terminal functions.

Refer to H1-03 to

H1-08: Functions for Terminals S3 to S8 on page 193

for details. .

Multi-Function Digital Outputs

The H2 parameters assign functions to digital output terminals M1-M2, M3-M4, M5-M6, P1-C1, and P2-PC digital input
terminal functions.

Refer to H2-01 to H2-05: Terminals M1-M2, M3-M4, M5-M6, P1-PC, and P1-P2 Function

Selection on page 197

for details.

DC Injection/

Position lock

DC Injection/
Position lock

Up/Down Command

Selected speed (other than leveling)

Speed

Safe disable (terminals H1/H2 on)

and Baseblock off (H1-

= 8/9)

DC Injection/
Position lock

DC Injection/
Position lock

Leveling speed has priority

Up/Down Command

Leveling speed

Selected speed (other than leveling)

Speed

Safe disable (terminals H1/H2 on)

and Baseblock off (H1-

= 8/9)

DC Injection/

position lock

DC Injection/
position lock

Up/Down Command

Leveling speed

Speed

Safe disable (terminals H1/H2 on)

and Baseblock off (H1-

= 8/9)