Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 434

C.9 MEMOBUS/Modbus Data Table
434
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
003DH
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
003EH
Output Speed
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-.
Refer to U: Monitors on page 404
for parameter details.
004BH
Drive status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPE)
bit 9
During Momentary Power Loss
bit A
Motor 2 Selected
bit B to D
Reserved
bit E
ComRef status, NetRef status
bit F
ComCtrl status, NetCtrl status
004CH to 007EH
Used for various monitors U1-, U4-, and U6-.
Refer to U: Monitors on page 404
for parameter details.
007FH
Alarm Code,
Refer to Alarm Register Contents on page 441
for alarm codes.
0080H to 0097H
Used for monitors U2-, U3-.
Refer to U: Monitors on page 404
for parameter details and
Refer to Fault Trace Contents on page 439
for register
value descriptions.
0098H, 0099H
U4-01 (Cumulative Operation Time)
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
009AH, 009BH
U4-03 (Cooling Fan Operation Time)
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00ACH
Speed Feedback (U1-05)
r/min units
00ADH
0.01% units
00AEH, 00AFH
Reserved
00B0H
Option Code Connected to CN5-A
Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
PG-F3 = 0x21
PG-E3 = 0x22
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5353H for “SS” if a SI-S3 option card is installed.
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
Output Speed After Soft Start
(U1-16)
r/min units
00B6H
0.01% units
00B7H
Speed Reference
r/min units
00B8H
0.01% units
00B9H to 00BEH
Reserved
00BFH
Lists the last to digits of operation error code oPE.
Register No.
Contents