C.9 MEMOBUS/Modbus Data Table

434

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

003DH

Communications Error Contents

<3>

bit 0

CRC Error

bit 1

Data Length Error

bit 2

Reserved

bit 3

Parity Error

bit 4

Overrun Error

bit 5

Framing Error

bit 6

Timeout

bit 7 to bit F

Reserved

003EH

Output Speed

r/min

<4>

003FH

0.01% units

0040H to 004AH

Used for various monitors U1-††.

Refer to U: Monitors on page 404

for parameter details.

004BH

Drive status (U1-12)
bit 0

During Run

bit 1

During Zero Speed

bit 2

During Reverse Run

bit 3

During Fault Reset Signal Input

bit 4

During Speed Agree

bit 5

Drive Ready

bit 6

Alarm

bit 7

Fault

bit 8

During Operation Error (oPE††)

bit 9

During Momentary Power Loss

bit A

Motor 2 Selected

bit B to D

Reserved

bit E

ComRef status, NetRef status

bit F

ComCtrl status, NetCtrl status

004CH to 007EH

Used for various monitors U1-††, U4-††, and U6-††.

Refer to U: Monitors on page 404

for parameter details.

007FH

Alarm Code,

Refer to Alarm Register Contents on page 441

for alarm codes.

0080H to 0097H

Used for monitors U2-††, U3-††.

Refer to U: Monitors on page 404

for parameter details and

Refer to Fault Trace Contents on page 439

for register

value descriptions.

0098H, 0099H

U4-01 (Cumulative Operation Time)
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.

009AH, 009BH

U4-03 (Cooling Fan Operation Time)
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.

009CH to 00AAH

Reserved

00ABH

Drive Rated Current

<2>

00ACH

Speed Feedback (U1-05)

r/min units

<4>

00ADH

0.01% units

00AEH, 00AFH

Reserved

00B0H

Option Code Connected to CN5-A

Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
PG-F3 = 0x21
PG-E3 = 0x22
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5353H for “SS” if a SI-S3 option card is installed.

00B1H

Reserved

00B2H

Option Code Connected to CN5-B

00B3H

Option Code Connected to CN5-C

00B4H

Reserved

00B5H

Output Speed After Soft Start

(U1-16)

r/min units

<4>

00B6H

0.01% units

00B7H

Speed Reference

r/min units

<4>

00B8H

0.01% units

00B9H to 00BEH

Reserved

00BFH

Lists the last to digits of operation error code oPE††.