5.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

201

P

a

ra

me

te

r De

ta

ils

5

Figure 5.22

Figure 5.22 Speed Detection 2 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 219

for more details.

Setting 6: Drive ready (READY)

Output closes whenever the drive is ready to operate the motor. The terminal will not close under the conditions listed
below, and any Up/Down commands will be disregarded.

• When the power is shut off
• During a fault
• When the internal power supply of the drive has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an overvoltage or undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
• When parameter L8-88 = 0 and at least one Safe Disable input is open

Setting 7: DC bus undervoltage

Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A
fault in the DC bus circuit will also cause the terminal to set for “DC bus undervoltage” to close.

Setting 8: During baseblock (N.O.)

Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.

Setting 9: Speed reference source

Displays the currently selected speed reference source.

Setting A: Up/Down command source

Displays the currently selected Up/Down command source.

Status

Description

Open

DC bus voltage is above the level set to L2-05

Closed

DC bus voltage has fallen below the trip level set to L2-05.

Status

Description

Open

Drive is not in a baseblock state.

Closed

Baseblock is being executed.

Status

Description

Open

Speed reference is provided from External reference 1 (b1-01).

Closed

Speed reference is being sourced from the digital operator.

Status

Description

Open

Up/Down command is provided from External reference 1 (b1-02).

Closed

Up/Down command is being sourced from the digital operator.