E2-04: number of motor poles, E2-05: motor line-to-line resistance, E2-06: motor leakage inductance – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 180: E2-07: motor iron-core saturation coefficient 1, E2-08: motor iron-core saturation coefficient 2, E2-09: motor mechanical loss, 5 e: motor parameters

5.5 E: Motor Parameters
180
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
load current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
Note: The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display
values in 0.01 A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.
■
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will
automatically be saved to E2-04.
■
E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is
automatically calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it
manually. When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
• E-type insulation: Multiply 0.92 times the resistance value (
Ω) listed on the test report at 75°C.
• B-type insulation: Multiply 0.92 times the resistance value (
Ω) listed on the test report at 75°C.
• F-type insulation: Multiply 0.87 times the resistance value (
Ω) listed on the test report at 115°C.
■
E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically
set during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
■
E2-07: Motor Iron-Core Saturation Coefficient 1
Sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully,
then this value is automatically calculated and set to E2-07. This coefficient is used when operating with constant output.
■
E2-08: Motor Iron-Core Saturation Coefficient 2
Sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully,
then this value is automatically and set to E2-08. This coefficient is used when operating with constant output.
■
E2-09: Motor Mechanical Loss
There is normally no need to change this parameter from the default value. This parameter sets to the motor mechanical
loss as a percentage of motor rated power (kW) capacity.
No.
Parameter Name
Setting Range
Default
E2-03
Motor No-Load Current
0 to [E2-01]
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E2-04
Number of Motor Poles
2 to 48
4
No.
Parameter Name
Setting Range
Default
E2-05
Motor Line-to-Line Resistance
0.000 to 65.000
Ω
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E2-06
Motor Leakage Inductance
0.0 to 40.0%
Determined by o2-04
No.
Parameter Name
Setting Range
Default
E2-07
Motor Iron-Core Saturation Coefficient 1
0.00 to 0.50
0.50
No.
Parameter Name
Setting Range
Default
E2-08
Motor Iron-Core Saturation Coefficient 2
E2-07 to 0.75
0.75