7.4 Drive Cooling Fans and Circulation Fans

326

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

3.

Make sure that the protective tube does not stick out beyond the fan guard.

4.

Double-check the relay connector to ensure that it is properly connected.

Cooling Fan Wiring: 2A0269, 2A0354, and 4A0225

1.

Position the protective tube so that the fan connector sits in the center of the protective tube.

2.

Insert the connector for fan B2 and guide the lead wire for fan B2 so the cable hook holds it in place. Insert the
connector for fan B1.

Figure 7.23

Figure 7.23 Cooling Fan Wiring: 2A0269, 2A0354, and 4A0225

3.

Make sure that the protective tube does not stick out beyond the fan guard.

Protective tube

C O M -

MON

Cable hook

Connector for fan B2

Connector for fan B1

Fan B2

Fan B1

Common_

TMonly