T1-04: motor rated current, T1-05: motor base frequency, T1-06: number of motor poles – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 116: T1-07: motor base speed, T1-08: pg number of pulses per revolution, T1-09: motor no-load current, 5 auto-tuning

4.5 Auto-Tuning
116
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
■
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Set the motor rated current between 50% and 100%
of the drive rated current for optimal performance in OLV or CLV. Enter the current at the motor base speed.
■
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used
or if the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after Auto-
Tuning is complete.
■
T1-06: Number of Motor Poles
Sets the number of motor poles according to the motor nameplate value.
■
T1-07: Motor Base Speed
Sets the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or if
the motor is used in the field weakening area, enter the speed at base frequency to T1-07.
■
T1-08: PG Number of Pulses Per Revolution
Sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor rotation.
Note: T1-08 will only be displayed in CLV.
■
T1-09: Motor No-Load Current
Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the
output power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave
this data at the default setting if the motor test report is not available.
No.
Parameter Name
Setting Range
Default
T1-04
Motor Rated Current
10 to 200% of drive rated current
Depending on o2-04
No.
Parameter Name
Setting Range
Default
T1-05
Motor Base Frequency
0.0 to 120.0 Hz
60.0 Hz
No.
Parameter Name
Setting Range
Default
T1-06
Number of Motor Poles
2 to 48
4
No.
Parameter Name
Setting Range
Default
T1-07
Motor Base Speed
0 to 24000 r/min
1750 r/min
No.
Parameter Name
Setting Range
Default
T1-08
PG Number of Pulses Per Revolution
0 to 60000 ppr
1024 ppr
No.
<1> The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display values in
0.01 A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.
Parameter Name
Setting Range
Default
T1-09
Motor No-Load Current
0 to [T1-04] A
(Max: 0 to 2999.9)
–