4.6 Setup Procedure for Elevator Applications

134

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

• Use a battery with a voltage higher than 250 Vdc for 200 V class drives or 500 Vdc for 400 V class drives and connect

it to the control power supply input (CN19). Alternatively use a 24 Vdc battery and an optional 24 V Backup Power
Supply Unit.

• Enable Light Load Direction Search (S4-01 = 1).

Using Separate Batteries for DC Bus and Control Power Supply, DC Bus Battery under 250
Vdc (500 Vdc)

Follow these instructions when using separate batteries for Rescue Operation with the battery for the DC bus having a
lower voltage than 250 Vdc for 200 V class drives and 500 Vdc for 400V class drives.

Wiring

Follow the wiring diagram shown in

Figure 4.26

. When connecting the battery for the control power supply to the

L1000E, use the 1.1 m cable packaged with the product. The connector cover must first be removed in order to access
connection port CN19 for the battery. Refer to

Connecting the Drive and Battery on page 137

for details.

Figure 4.21

Figure 4.26 Wiring Two Batteries for DC Bus and Control Power Supply (DC Bus Battery is less than 250 V)

Operation Sequence

Starting Rescue Operation

1.

Open contactor B and wait at least 5 seconds.

2.

Set the input terminal programmed for Rescue Operation (H1-†† = 55).

3.

Close contactors A and C.

4.

Set the Up/Down command.

Ending Rescue Operation

1.

After the car has stopped, open contactors A and C.

2.

Clear the input terminal set for Rescue Operation (H1-†† = 55).

3.

Wait at least 0.5 s and then close contactor B to return to operation with normal power supply.

-

Magnetic Contactor Sequence

L1000E

Control

circuit

Power supply

Battery for DC bus

DC bus power supply

Battery for

control circuit

L1

L2

L3

CN19

1

4

W/T3

V/T2

U/T1

R/L1

S/L2

T/L3

B1

+2

+1

B2

SC

H1-

ڧڧ = 55

(Rescue Operation)

S

3

to S

8

48 to 340 Vdc
96 to 680 Vdc

250 to 340 Vdc

(500 to 680 Vdc

Magnetic Contactor A

Magnetic Contactor B

Magnetic Contactor C

H1-

ڧڧ = 55

(Rescue Operation)

Magnetic Contactor B

Magnetic Contactor A

Magnetic Contactor C

5 s

0.5 s