Fuse/fuse holder, Attachment for external heatsink mounting, 5 installing peripheral devices – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 355: Table 8.11 input fuses

Advertising
background image

8.5 Installing Peripheral Devices

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

355

Per

iphe

ra

l De

vi

ce

s &

Optio

n

s

8

Fuse/Fuse Holder

Yaskawa recommends installing a fuse to the input side of the drive to prevent damage to the drive if a short circuit
occurs.

Select the appropriate fuse from the table below.

Table 8.11 Input Fuses

Attachment for External Heatsink Mounting

An external attachment can be used to project the heatsink outside of an enclosure to ensure that there is sufficient air
circulation around the heatsink. Contact a Yaskawa sales representative or Yaskawa directly for more information on this
attachment.

Installing a Motor Thermal Overload (oL) Relay on the Drive Output

Motor thermal overload relays protect the motor by disconnecting power lines to the motor due to a motor overload
condition.

Drive Model

CIMR-LE

L1000E

Nominal Output

Power HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.

Time Delay Fuse

Rating Amps

<2>

<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.

Non-time Delay

Fuse Rating Amps

<3>

<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.

Bussmann

Semi-conductor Fuse Rating

(Fuse Ampere)

<4>

<4> When using semiconductor fuses, Bussmann FWH is required for UL compliance.

<5> Class L fuse is also approved for this rating.

240 V Models

2A0018

5

15.6

25

25

40

FWH-90B (90)

2A0022

7.5

18.9

35

30

50

FWH-90B (90)

2A0031

10

28

50

40

75

FWH-100B (100)

2A0041

15

37

60

60

100

FWH-200B (200)

2A0059

20

52

100

90

150

FWH-200B (200)

2A0075

25

68

125

110

200

FWH-200B (200)

2A0094

30

80

150

125

225

FWH-300A (300)

2A0106

40

82

150

125

225

FWH-300A (300)

2A0144

50

111

200

175

250

FWH-350A (350)

2A0181

60

136

250

225

350

FWH-400A (400)

2A0225

75

164

300

250

450

FWH-400A (400)

2A0269

100

200

400

350

600

FWH-600A (600)

2A0354

125

271

500

450

800

FWH-700A (700)

2A0432

150

324

600

500

900

<5>

FWH-800A (800)

480 V Models

4A0009

5

8.2

15

12

20

FWH-90B (90)

4A0012

7.5

10.4

20

17.5

30

FWH-90B (90)

4A0019

10

15

30

25

40

FWH-80B (80)

4A0023

15

20

40

35

60

FWH-100B (100)

4A0030

20

29

50

50

80

FWH-125B (125)

4A0039

25

39

75

60

110

FWH-200B (200)

4A0049

30

44

75

75

125

FWH-250A (250)

4A0056

40

43

75

75

125

FWH-250A (250)

4A0075

50

58

100

100

150

FWH-250A (250)

4A0094

60

71

125

110

200

FWH-250A (250)

4A0114

75

86

150

150

250

FWH-250A (250)

4A0140

100

105

175

175

300

FWH-350A (350)

4A0188

125

142

225

225

400

FWH-400A (400)

4A0225

150

170

250

250

500

FWH-500A (500)

4A0260

175

207

350

350

600

FWH-600A (600)