4 d: reference settings, D1: speed reference, For details – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 174: D1-18: speed reference selection mode

Advertising
background image

174

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

5.4 d: Reference Settings

5.4 d: Reference Settings

The d parameters determine the speed of the elevator including the speed reference and Field Forcing settings for motor
response.

d1: Speed Reference

The d1 parameter group is used to set the speed reference. Switch the multi-function input contact terminals to create a
multi-step speed sequence using the various references set to the d1 parameters.

d1-01 to d1-08: Speed References 1 to 8

These parameters set speed references 1 through 8. Each of these speed reference values can be selected using digital
inputs programmed for multi-speed selection (H1-†† = 3, 4, 5).

Refer to Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on page 121

for details.

d1-18: Speed Reference Selection Mode

Sets the priority of the speed reference inputs.

NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-

01 (Speed Reference Selection), or H1-

††

(Multi-Function Digital Inputs). If the RUN command is on when changing any of these

settings, the motor may unexpectedly start running, and could result in injury.

Setting 0: Use multi-speed references d1-01 to d1-08

Up to eight separate preset speed references can be programmed to the drive using parameters d1-01 through d1-08 and
can be selected using binary coded digital inputs. When d1-18 is set to “0”, parameters d1-19 through d1-23 are not
displayed.

Refer to Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on page 121

for details.

Setting 1: High speed reference has priority

Six different speeds (d1-19 to d1-23, d1-26) can be programmed to the drive and can be selected using dedicated digital
inputs. Each of the speed references set to d1-19 through d1-23 takes priority over the leveling speed set to d1-26. When
d1-18 is set to “1”, parameter d1-01 to d1-08 are not displayed.

Refer to Separate Speed Inputs (d1-18 = 1 or 2) on

page 122

for details.

Setting 2: Leveling speed reference has priority

Six different speeds (d1-19 to d1-23, d1-26) can be programmed to the drive and can be selected using dedicated digital
inputs. The leveling speed reference in d1-26, however, takes priority over all other speed references when enabled via
one of the multi-function input terminals (H1-††= 53). When d1-18 is set to “2”, parameters d1-01 to d1-08 are not
displayed.

Refer to Separate Speed Inputs (d1-18 = 1 or 2) on page 122

for details.

Setting 3: Use multi-speed references d1-02 to d1-08, no speed selection stops the drive

Up to seven separate preset speed references can be programmed to the drive using parameters d1-02 through d1-08 can
be selected using binary coded digital inputs. When d1-18 is set to “3”, parameters d1-19 through d1-23 are not displayed.

Refer to Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3) on page 121

for details.

No.

Parameter Name

Setting Range

Default

d1-01 to d1-08

<1> Setting units and the default setting are determined by parameter o1-03.

Refer to Defaults and Setting Ranges by Display Unit Selection (o1-

03) on page 416

for details.

Speed Reference 1 to 8

0.00 to 100.00%

<1>

0.00%

<1>

No.

Parameter Name

Setting Range

Default

d1-18

Speed Reference Selection Mode

0 to 3

0

Advertising