D.2 ul standards – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 452

Advertising
background image

D.2 UL Standards

452

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

4A0039

R/L1, S/L2, T/L3

16

(6)

6.0 to 16

(10 to 6)

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

10

(8)

6.0 to 16

(10 to 6)

–, +1, +2

16

(6)

B1, B2

6.0 to 10

(10 to 8)

M5

2.7 to 3.0

(23.9 to 26.6)

16

(6)

6.0 to 16

(10 to 6)

M6

4 to 6

(35.4 to 53.1)

4A0049

R/L1, S/L2, T/L3

16

(6)

16 to 25

(6 to 4)

M6

4 to 6

(35.4 to 53.1)

U/T1, V/T2, W/T3

16

(6)

16 to 25

(6 to 4)

–, +1, +2

16 to 25

(6 to 4)

B1, B2

6.0 to 10

(10 to 8)

M5

2 to 2.5

(17.7 to 22.1)

16

(6)

10 to 16

(8 to 6)

M6

4 to 6

(35.4 to 53.1)

4A0056

R/L1, S/L2, T/L3

25

(4)

6.0 to 50

(10 to 1/0)

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

25

(4)

6.0 to 50

(10 to 1/0)

–, +1

16 to 35

(6 to 1)

B1, B2

10 to 16

(8 to 4)

16

(6)

10 to 16

(8 to 6)

4A0075

R/L1, S/L2, T/L3

35

(3)

6.0 to 70

(10 to 3/0)

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

35

(3)

6.0 to 70

(10 to 3/0)

–, +1

25 to 35

(4 to 1)

B1, B2

16 to 25

(6 to 3)

16

(6)

16

to 25

(6)

4A0094

R/L1, S/L2, T/L3

35

(2)

16 to 120

(6 to 250)

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

50

(1)

16 to 120

(6 to 250)

–, +1

25 to 50

(3 to 1/0)

+3

16 to 50

(6 to 1/0)

25

(4)

16 to 25

(6 to 4)

4A0114

R/L1, S/L2, T/L3

70

(1/0)

16 to 120

(6 to 250)

M8

9 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

70

(1/0)

16 to 120

(6 to 250)

–, +1

25 to 50

(3 to 1/0)

+3

25 to 50

(4 to 1/0)

25

(4)

16 to 25

(6 to 4)

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N•m (lb.in.)

Advertising