8.5 Installing Peripheral Devices

352

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Connecting a DC Link Choke

A DC link choke can be installed to drive models 2A0018 to 2A0094 and 4A0009 to 4A0049. When installing a DC link
choke, remove the jumper between terminals +1 and +2 (terminals are jumpered for shipment). The jumper must be
installed if not using a DC link choke. Refer to

Figure 8.21

for an example of DC link choke wiring.

Figure 8.19

Figure 8.21 Connecting a DC Link Choke

Connecting a Surge Absorber

A surge absorber suppresses surge voltage generated from switching an inductive load near the drive. Inductive loads
include magnetic contactors, relays, valves, solenoids, and brakes. Always use a surge absorber or diode when operating
with an inductive load.

WARNING! Fire Hazard. Due to surge absorber short circuit on drive output terminals U/T1, V/T2, and W/T3, do not connect surge

absorbers to the drive output power terminals. Failure to comply may result in serious injury or death by fire or flying debris.

Connecting a Noise Filter

Input-Side Noise Filter

Drive outputs generate noise as a result of high-speed switching. This noise flows from inside the drive back to the power
supply, possibly affecting other equipment. Installing a noise filter to the input side of the drive can reduce the amount of
noise flowing back into the power supply. This also prevents noise from entering the drive from the power supply.

• Use a noise filter specifically designed for AC drives.
• Install the noise filter as close as possible to the drive.

Figure 8.20

Figure 8.22 Input-Side Noise Filter (Three-Phase 200/400 V)

A – Power supply

C – Drive

B – MCCB

D – DC Link Choke

A – Power supply

C – Drive

B – Input-side noise filter

(model LNFD-††)